CVE-2025-32830 — Technical Security Advisory & CVSS Profile
A vulnerability has been identified in TeleControl Server Basic (All versions < V3.1.2.2). The affected application is vulnerable to SQL injection through the internally used 'UnlockProject' method. This could allow an authenticated remote attacker to bypass authorization controls, to read from and write to the application's database and execute code with "NT AUTHORITY\NetworkService" permissions. A successful attack requires the attacker to be able to access port 8000 on a system where a vulnerable version of the affected application is executed on.
Technical Metadata
| Identifier | CVE-2025-32830 |
|---|---|
| Base Severity / Score | HIGH (8.8 / 10.0) |
| CVSS Vector | CVSS:3.1/AV:N/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H |
| Weakness Classification | CWE-89 |
| Archive Categories | HIGH Advisories · 2025 Index |
Operational Mitigation Guidance
Prioritize remediation in the next maintenance cycle. Validate affected dependency versions in SBOM manifests and review inbound access controls. For architectural isolation principles, review per-process namespace isolation.